XLPE/AWA/PVC Single core

To BS6724, 0.6/1kv

Range of temperature: Installation minimum 0 c  
  Normal operating, maximum 90 c  
  Short circuits, maximum 250 c

 

XLPE insulated aluminium wire armoured, PVC sheathed cable with copper conductor.
 
 
 
 
XLPE/AWA/PVC Single Core Technical Data

Cross

Conductor

 

Thickness

 

Outer

Aluminium

Weight

Conductor

Armour

Bending

Section

diameter

of

of

of

diameter

wire

of cable

resistance

resistance

radius

 

 

insulation

sheath

bedding

(D)

diameter

 

at 20 C

at 20 C

min at

 

nom

nom

nom

nom

nom

nom

nom

max

max

installation

mm˛

mm

mm

mm

mm

mm

mm

kg/km

ohm/km

ohm/km

mm

1 x 50

8.8

1.0

1.5

0.8

18.0

0.9

690

0.387

1.30

6 x D

1 x 70

10.6

1.1

1.5

0.8

20.0

1.3

960

0.268

0.75

6 x D

1 x 95

12.5

1.1

1.6

0.8

22.0

1.3

1215

0.193

0.67

6 x D

1 x 120

14

1.2

1.6

0.8

24.0

1.3

1490

0.153

0.61

6 x D

1 x 150

15.6

1.4

1.7

1.0

27.0

1.6

1850

0.124

0.42

6 x D

1 x 185

17.5

1.6

1.8

1.0

30.0

1.6

2280

0.0991

0.38

6 x D

1 x 240

20

1.7

1.8

1.0

33.0

1.6

2850

0.0754

0.34

6 x D

1 x 300

22.5

1.8

1.9

1.0

36.0

1.6

3480

0.0601

0.31

6 x D

1 x 400

25.5

2.0

2.0

1.2

41.0

2.0

4580

0.0470

0.22

6 x D

1 x 500

28.4

2.2

2.1

1.2

44.0

2.0

5680

0.0366

0.20

6 x D

1 x 630

32.5

2.4

2.2

1.2

50.0

2.0

7160

0.0283

0.18

6 x D

1 x 800

36.8

2.6

2.4

1.4

55.0

2.5

9100

0.0221

0.13

6 x D

1 x 1000

41.4

2.8

2.5

1.4

60.0

2.5

11400

0.0176

0.12

6 x D

Conductor:
Plain annealed copper complying with BS6360, Class 2. 50-1000mm˛ circular stranded.
Insulation:
Extruded XLPE complying with BS7655: section 1.3, type GP8.
Core identification:
Black
Bedding:
Extruded layer of polymeric compound having a tensile strength of not less than 4 N/mm˛ and an elongation at break not less than 50%.
Armour:
A single layer of Aluminium wires is laid in a left hand direction.
Sheath:
Black PVC complying with BS 7655: Section 4.2, type 9.