XLPE/SWA/PVC Auxiliary

To BS5467, 0.6/1kv

Range of temperature: Installation minimum 0 c  
  Normal operating, maximum 90 c  
  Short circuits, maximum 250 c

 

XLPE insulated steel wire armoured, PVC sheathed cable with copper conductors.
 
 
 
 
 
XLPE/SWA/PVC Auxiliary Technical Data

Cross

Conductor

 

Thickness

 

Outer

Steel

Weight

Conductor

Armour

Bending

Section

diameter

of

of

of

diameter

wire

of cable

resistance

resistance

radius

 

 

insulation

sheath

bedding

 

diameter

 

at 20 C

at 20 C

min at

 

nom

nom

nom

nom

nom

nom

nom

max

max

installation

mm˛

mm

mm

mm

mm

mm

mm

kg/km

ohm/km

ohm/km

mm

7 X 1.5

1.55

0.6

1.4

0.8

15.0

0.9

440

12.1

7.5

6 x D

12 X 1.5

1.55

0.6

1.5

0.8

20.0

1.3

750

12.1

4

6 x D

19 X 1.5

1.55

0.6

1.6

0.8

22.0

1.3

980

12.1

3.5

6 x D

27 X 1.5

1.55

0.6

1.7

1.0

27.0

1.6

1430

12.1

2.3

6 x D

37 X 1.5

1.55

0.6

1.7

1.0

30.0

1.6

1730

12.1

2

6 x D

48 X 1.5

1.55

0.6

1.8

1.0

33.0

1.6

2900

12.1

1.8

6 x D

7 X 2.5

2

0.7

1.4

0.8

16.0

0.9

550

7.41

6.3

6 x D

12 X 2.5

2

0.7

1.6

0.8

22.0

1.3

935

7.41

3.5

6 x D

19 X 2.5

2

0.7

1.7

1.0

26.0

1.6

1420

7.41

2.3

6 x D

27 X 2.5

2

0.7

1.8

1.0

30.0

1.6

1830

7.41

1.9

6 x D

37 X 2.5

2

0.7

1.8

1.0

33.0

1.6

2220

7.41

1.7

6 x D

48 X 2.5

2

0.7

2.0

1.2

39.0

2.0

3000

7.41

1.2

6 x D

7 X 4

2

0.7

1.5

0.8

20.0

1.3

890

4.61

4

6 x D

12 X 4

2

0.7

1.6

1.0

26.0

1.6

1530

4.61

2.3

6 x D

19 X 4

2

0.7

1.7

1.0

29.0

1.7

2000

4.61

2

6 x D

27 X 4

2

0.7

1.9

1.0

34.0

1.6

2600

4.61

1.7

6 x D

37 X 4

2

0.7

2.0

1.2

39.0

2.0

3600

4.61

1.2

6 x D

48 X 4

2

0.7

2.1

1.2

44.0

2.0

4400

4.61

1

6 x D

Conductor:
Plain annealed copper complying with BS 6360, 1.5 - 16mm˛ circular stranded, 25 - 400 mm˛ shaped stranded.
Insulation:
Extruded XLPE complying with BS7655: section 1.3, type GP8.
Core identification:
White with black printed numbers on the cores
Lay Up & Bedding:
The cores are laid up in concentric layers and covered with an extruded layer of polymeric compound having a tensile strength of not less than 4N/mm˛ and an elongation at break not less than 50%
Armour:
A single layer of galvanised steel wires is laid in a left hand direction.
Sheath:
Black PVC complying with BS7655: Section 4.2, type 9.
Multi-Core XLPE insulated/PVC/SWA/PVC sheathed to BS5467 600/1000V