XLPE/LSHF/SWA 4 core

To BS6724, 0.6/1kv

Range of temperature: Installation minimum 0 c  
  Normal operating, maximum 90 c  
  Short circuits, maximum 250 c

 

XLPE insulated LSHF bedded steel wire armoured, LSHF sheathed cable with copper conductors. Halogen free cable with low emission of smoke and fume.
 
 
 
XLPE/LSHF/SWA  4 Core Technical Data

Cross

Conductor

 

Thickness

 

Outer

Steel

Weight

Conductor

Armour

Bending

Section

diameter

of

of

of

diameter

wire

of cable

resistance

resistance

radius

 

 

insulation

sheath

bedding

 

diameter

 

at 20 C

at 20 C

min at

 

nom

nom

nom

nom

nom

nom

nom

max

max

installation

mm˛

mm

mm

mm

mm

mm

mm

kg/km

ohm/km

ohm/km

mm

4 X 1.5

1.55

0.6

1.3

0.8

13.0

0.9

350

12.1

8.8

6 x D

4 X 2.5

2

0.7

1.4

0.8

14.0

0.9

410

7.41

7.7

6 x D

4 X 4

2.5

0.7

1.4

0.8

16.0

0.9

515

4.61

6.8

6 x D

4 X 6

3

0.7

1.5

0.8

18.0

1.3

730

3.08

4.3

6 x D

4 X 10

3.9

0.7

1.5

0.8

20.0

1.3

970

1.83

3.7

6 x D

4 X 16

4.8

0.7

1.6

0.8

23.0

1.3

1290

1.15

3.1

6 x D

4 X 25

 

0.9

1.7

0.8

28.0

1.6

1990

0.727

2.3

8 x D

4 X 35

 

0.9

1.8

0.8

31.0

1.6

2500

0.524

2

8 x D

4 X 50

 

1.0

1.9

0.8

34.0

1.6

3100

0.387

1.8

8 x D

4 X 70

 

1.1

2.1

0.8

39.0

2.0

4350

0.268

1.2

8 x D

4 X 95

 

1.1

2.2

0.8

43.0

2.0

5500

0.193

1.1

8 x D

4 X 120

 

1.2

2.3

0.8

47.0

2.5

7000

0.153

0.76

8 x D

4 X 150

 

1.4

2.4

0.8

52.0

2.5

8350

0.124

0.68

8 x D

4 X 185

 

1.6

2.6

0.8

57.0

2.5

10200

0.0991

0.61

8 x D

4 X 240

 

1.7

2.7

0.8

63.0

2.5

12800

0.0754

0.54

8 x D

4 X 300

 

1.8

2.9

0.8

69.0

2.5

15500

0.0601

0.49

8 x D

4 X 400

 

2.0

3.2

0.8

79.0

3.2

20300

0.0470

0.35

8 x D

Conductor:
Plain annealed copper complying with BS6360, Class 2. 1.5-16mm˛ circular stranded, 25-400mm˛ shaped stranded.
Insulation:
Extruded XLPE complying with BS7655: section 1.3, type GP8.
Core identification:
Brown, Black, Blue & Grey
Lay Up:
The cores are laid up in a right hand direction.
Armour:
A single layer of galvanized steel wires is laid in a left hand direction.
Sheath:
An extruded layer of synthetic material according to BS7655: Section 6.1, type LTS1.
Multi-Core XLPE insulated/PVC/SWA/PVC sheathed to BS5467 600/1000V