Fire Performance Cable
CWZ Fire cable to BS5839-1 : 2002
Cat. 300/500v
![]()

CWZ Fire Performance Cable Technical Data
|
Cross |
Outer diameter |
Current |
Voltage drop |
Weight |
||
|
section |
(approx) |
rating |
(V/A x km) |
approx |
||
|
|
|
|
||||
|
|
|
AC/ DC |
AC |
|
||
|
c x mm˛ |
Min. (mm) |
Max. (mm) |
(A) |
2 core loaded |
3 core loaded |
kg/km |
|
2 x 1.0 |
6.9 |
8.2 |
15 |
44 |
87 |
|
|
2 x 1.5 |
7.3 |
8.7 |
19.5 |
29 |
103 |
|
|
2 x 2.5 |
9.2 |
10.8 |
27 |
18 |
164 |
|
|
2 x 4.0 |
1.5 |
12.3 |
36 |
11 |
247 |
|
|
3 x 1.0 |
7.3 |
9.6 |
13.5 |
38 |
102 |
|
|
3 x 1.5 |
7.8 |
10 |
17.5 |
25 |
123 |
|
|
3 x 2.5 |
9.8 |
12.7 |
24 |
15 |
198 |
|
|
3 x 4.0 |
11.2 |
14.1 |
32 |
9.5 |
295 |
|
|
4 x 1.0 |
8.2 |
10.6 |
13.5 |
38 |
125 |
|
|
4 x 1.5 |
8.7 |
11.2 |
17.5 |
25 |
151 |
|
|
4 x 2.5 |
10.9 |
14.1 |
24 |
15 |
242 |
|
|
4 x 4.0 |
12.4 |
15.3 |
32 |
9.5 |
362 |
|
Standards: BS7629 part 1, BS5839-1: 2002, Cat. Standard.
Fire resistant: BS6387 CWZ, BS8434-1: 2003, BS EN 50200 PH 30
Flame retardant: BS EN 50265 1 & 2.1, IEC 60332 part1
Low smoke: BS EN 50268, IEC 61034
Halogen free: BS EN 50267, IEC 60754
Low toxicity: BS EN 50267, IEC 60754
Low corrosivity: BS EN 50267, IEC 60754
Temperature range: - 20 to + 60 °C
BS6387 CWZ provides test to:
Category C: Exposed to fire @ 950 °C for 3 hours. Category W: Exposed to fire @ 650 °C for 15 mins then exposed to fire @ 650 °C with water for 15 mins. Category Z: Exposed to fire @ 650 °C for 15 mins then exposed to fire @ 650 °C with mechanical shock for 15 mins. The current and voltage drops and data above are indicated for continuous duty operation. They are as defined in BS 7671: 2001, table 4D2A and apply to: Maximum conductor temperature = 70 °C Nominal frequencies = 50 - 60 Hz On cable in air, clipped direct at ambient air temperature = 30 °C Voltage drop: The data shown above is based on Cos φ = 1 For other laying conditions refer to BS7671: 2001 standard.